Emergency and Exit Light Testing Perth

Power On provide emergency evacuation lighting testing to conform to
Australian standards AS2293. The standards require regular periodical 6
monthly testing including:

  • Revamping of expired tubes and lamps
  • Adequate electrical supply
  • Discharge tests
  • Visual inspection
  • Replacement of non compliant fitting and batteries
  • Log / record of fitting details and test procedures

Electrical Testing Perth

Inspection and testing to as AS 2293.2

Six – Monthly Procedures

  • Visual check of all emergency and exit lights for mains operation.
  • Check for operation of maintained exit lights.
  • Where manual discharge test facility is present, operate test switch / circuit breaker to simulate a power failure.
  • The emergency and exit lights shall remain illuminated for not less than 90miniutes.
  • Restore the emergency and exit lights to normal charging condition.
  • Check operation of all maintained exit lights and all charge indicators.
  • Report any failures on test sheets and service repair reports.

Twelve – Monthly Procedures

  • Carry out all checks as per six-monthly procedures.
  • Clean all emergency and exit lighting diffusers as required.
  • Visual check to ensure that the emergency and exit lighting operates in correct relationship to the normal lighting in the designated areas.
  • Replacement batteries are to be of the same type and ampere – hour capacity.
  • Discharge time for new batteries shall be 1.33 of the 90 minute discharge test (Two Hours).